Description
Designed as an economical and reliable protection against high-voltage transients and surges, and other electrical noise, produced for example by lightning, switching and electrical noise on AC or DC power lines.
Reactive 230Vac, 3A Maximum Line Filter
Description
Designed as an economical and reliable protection against high-voltage transients and surges, and other electrical noise, produced for example by lightning, switching and electrical noise on AC or DC power lines.
TYPE | IN-LF | |
Inductance | 2 x 1.8mH | |
Capacitance | 0.1µF | |
2 x 3300ρF | ||
VDR | Maximum | Voltage 3 x 275Vac |
Clamping Speed | 20µs | |
AC Voltage Range | 210~250Vac | |
(Other Voltage Ranges Available) | ||
Maximum Total Load | 3A (Other Ratings Available) | |
Leakage Current | <1mA @ 230Vac | |
Operating Temperature | 0~70°C @ 3A | |
Storage Temperature | -20~80°C | |
Operating Ambient Humidity | 5~85% RH Max, Non-condensing | |
DIN Rail Mounting | Fits all Available EN Mounting Rails | |
Dimensions | L=78mm, W=45mm, H=48mm |