TWI-FO / TWN-FO – DC to Frequency Transmitters
Brand: Intech
$355.00 Excl. GST
All prices are in NZ$, and GST exclusive and are subject to change without notice.
Product Details
Description
The TWI-FO and TWN-FO are designed as a low cost alternative to expensive A/D cards on PLC’s, computers and data acquisition systems.
The TWI-FO and TWN-FO convert and analogue signal into a linear, frequency output signal, with a 50:50 mark space ratio. Ideally designed to be used with a PLC to convert a 4~20mA signal into a 10~1010Hz frequency, (Other calibrations available) allowing direct connection into a digital input on a PLC (Use with interrupts) and powered by the PLC’s 24Vdc power supply.
TWI-FO / TWN-FO Features
- PLC interface
- Converts 4~20mA signal into a frequency for direct conversion into a digital input
- Isolated input to output 1.6kV for TWI-FO
- High accuracy
- LED indication of frequency output
- Easy to install
- Compact DIN rail mount enclosure
- Reverse polarity protection
- Externally accessible span and zero adjustments
Note: The conversion from TWN-FO to TWI-FO is easily achieved by the removal of two internal links.
Technical Specs
| TYPE | TWI-FO | |
| Input | Current | Standard: 4~20mA |
| Input Resistance = 25Ω | ||
| Options: 0~5mA, 1~5mA, 0~10mA, 2~10mA, 0~20mA, 0~50mA, 10~50mA | ||
| Voltage | Options: 0~5V, 1~5V, 0~10V, 2~10V | |
| Min Input Resistance = 200kΩ | ||
| Other inputs available on request | ||
| Output Ranges | Standard | 10~1010Hz |
| Options, J1=0 | 0~3.9Hz, 0~7.8Hz, 0~15.6Hz, 0~31.3Hz, 0~62.5Hz, 0~125Hz, 0~250Hz, 0~500Hz, 0~1kHz, 0~2kHz, 0~4kHz, 0~8kHz | |
| Options, J1=C | 0~3.13Hz, 0~6.25Hz, 0~12.5Hz, 0~25Hz, 0~50Hz, 0~100Hz, 0~200Hz, 0~400Hz, 0~800Hz, 0~1.6kHz, 0~3.2kHz, 0~6.4kHz | |
| Other outputs available on request, with or without offsets | ||
| Function | Squarewave Output; 50:50 Mark / Space Ratio | |
| Amplitude | (Power Supply 2) - 2V (No Load) | |
| Load | Limited to Sink / Source 100mA @ 24Vdc (50mA @ 12Vdc) Maximum load = 100mA @ 24Vdc Suitable for most optocoupler inputs Other variations available on request |
|
| Power Supply (1 & 2) | 11~28Vdc | |
| Current Usage | TWI-FO | P/S1 = 20mA, P/S2 = 20mA |
| TWN-FO | 40mA | |
| Supply Voltage Sensitivity | <±0.001%/V FSO | |
| Accurate to | <±0.1% FSO Typical | |
| Linearity & Repeatability | <±0.1% FSO Typical | |
| Ambient Drift | <±0.02%/C FSO Typical | |
| Noise Immunity | 125dB CMRR Average (1600Vdc Limit) - TWI-FO Only | |
| EMC Compliances | Emissions EN 55022-A, Immunity EN 50082-1, <1% Effect FSO Typical | |
| Isolation Test Voltage - TWI-FO Only | Input to Output 1600Vdc for 1min | |
| Response Time | 200msec Typical (10 to 90% 50msec Typical) | |
| Operating Temperature | 0°C~70°C | |
| Storage Temperature | -20°C~80°C | |
| Operating Humidity | 5~85%RH Max, Non-Condensing | |
| Dimensions and Construction | L=79, W=22.5, H=85mm, Polyamide Thermoplastic Rail Mount Enclosure | |