- Controller in 1 with input 3 points, setting 3 points, and output 3 points.
- Can make CH2 and CH3 follow CH1.
- Can select program function (optional).
- Can select event output (optional).
- Can select remote setting input (optional).
- Can select analog output (optional).
- Can select communication function (optional)
- Has simple dustproof drip-proof structure.
MR13 – 3 Input/Output Controller
The MR13 is a 3 channel controller with simultaneous 3-channel display.
Features
- 3-channel controller, 3-channel input, 3-channel setting and simultaneous 3-channel display
- Accuracy: ± (0.3% FS + 1 digit)
- Follow-up type PV input function
- Follow-up type SV setting function
- Remote/local and DI input function
- Programmable 1 pattern with 9-step function
- Expert PID which gives remarkably improved PID control efficiency; overshoot and undershoot are controlled effectively
- Interface RS232C/RS485
Brand: SHIMADEN
Usually in stock
Request a quoteScroll down for product range
Display | |
LED display | PV display 7-segment LED green 4 digits 3 channels to be displayed individually.
SV display 7-segment LED orange 4 digits CH display 7-segment LED orange 1 digit |
Action display LED |
Control output display: 3 – OUT1, OUT2, OUT3 Auto tuning: 1 – AT Follow type SV display: 1 – FLW Program RUN: 1 – RUN Event output display: 3 – EV1, EV2, EV3 Remote input display: 1 – REM Communication display: 1 – COM |
Display accuracy | ±(0.3%FS + 1 digit) Standard accuracy |
Temperature range in which accuracy is maintained | 23°C±5°C |
Display resolution | Depends on measuring range (0.001, 0.01, 0.1, 1) |
Sampling cycle | 0.5 seconds |
Measured value display range | –10% to 110% of measuring range |
Setting | |
Setting | By 6 front key operation |
Setting range | Same as measuring range |
Higher/lower limit setting limiter | Higher and lower limits to be set separately; free within measuring range (Lower limit < higher limit) |
Follow type SV setting | SV of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.) |
Input | |
Input type has to be the same for 3 channels (measuring rangecan be selected individually). | |
Thermocouple | B, R, S, K, E, J, T, N, PL II, WRe5-26, {L, U (DIN43710)} (Multiple input, multiple range. Refer to measuring range code table.) |
External resistance | 100Ω maximum |
Input impedance | 500kΩ minimum |
Burnout | Standard feature (up scale) Cold junction temperature compensation accuracy: ±2.0 °C (5~45 °C) |
R.T.D | JIS Pt100/JPt100 3-wire type (Multiple range. Refer to measuring range code table.) |
Amperage | Approx. 0.25 mA |
Lead wire tolerable resistance | 5Ω maximum/wire |
Voltage | ±10, 0~10, 0~20, 0~50, 10~50, 0~100mV DC, or ±1, 0~1, 0~2, 0~5, 1~5, 0~10V DC (Multiple input, programmable range. Refer to measuring range code table.) |
Input impedance | 500kΩ minimum |
Current | 4~20, 0~20mA DC (Multiple input, programmable range. Refer to measuring range code table.) |
Receiving impedance | 250Ω |
Sampling cycle | 0.5 seconds |
PV bias | ±1999 units |
PV filter | OFF, 1~100 seconds |
Follow type PV input | PV input of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.) |
Isolation | Insulated between input and various outputs (not insulated between input and system, remote input and DI input) |
Control | |
Control mode | Expert PID control with auto tuning function |
Proportional band (P) | OFF, 0.1~999.9%FS (OFF=ON/OFF action) |
Integral time (I) | OFF, 1~6000s (OFF=P, PD action with manual reset) |
Derivative time (D) | OFF, 1~3600s (OFF=P, PI action) |
Manual reset | ±50.0% |
ON/OFF hysteresis | 1~999 units |
Proportional cycle | 0.5~120.0 seconds (0.5 sec. is unit for setting.) |
Control output characteristics: | RA/DA selectable (set to RA when shipped) |
Output limiter | Higher limit, lower limit 0.0~100.0% (lower limit < Higher limit) |
Soft start | OFF, ON (Fixed to 10 sec.; Valid when power is turned on, RTS RUN, and when returned from scaleover.) |
Control output/rating | |
Output specification has to be the same for 3 channels. | |
Contact output (Y) | 1a 240V AC 2.5A/resistive load |
Current output (I) | 4~20mA, 0~10mA DC/load resistance 600Ω maximum. |
SSR drive voltage output (P) | 15V±3V DC/Load current 20mA maximum |
Voltage output (V) | 0~10V DC/Load current 2mA maximum |
Operation output updating cycle | 0.5 second |
Isolation | Insulated between control output and system and input (not insulated between control output I, P or V and analog output) |
Event output (optional) | |
Number of outputs | 3 -EV1, EV2, EV3 (Selectable from CH1, CH2 and CH3, individual setting, individual output) |
Output rating | Contact output 1a (common) 240V AC / 1A (resistive load) |
Setting | Individual setting
0) NON: Not assigned |
Hysteresis | 1~999 units (when DEV or PV has been selected) |
Standby action | Selectable (when DEV or PV has been selected) |
Action delay time | OFF, 1~9999 seconds (when DEV or PV has been selected) |
Isolation | Insulated between alarm output and various inputs/outputs and system |
Remote setting (optional, selectable between this function and DI) | |
Setting signal | 1~5V, 0~10V, 4~20mA |
Setting range | Same as measuring range |
Accuracy of setting | ±(0.3%FS + 1) digit |
Channel for setting | Selectable from CH1, CH2 and CH3 |
Remote scaling | Within measuring range (inverted scaling possible) |
Remote bias | –1999~5000 units |
Remote filter | OFF, 1~100 seconds |
Sampling time | 0.5 second |
Isolation | Insulated between remote input and various outputs (not insulated from system and various inputs) |
External control input (DI) (optional, selectable between this function and remote setting) | |
Number of input point | 1 |
Input rating | Non-voltage contact, open collector input (about 5V/0.4mA DC impress) |
Action type | NON, FLW (follow type SV), RST/ RUN, HLD and ADV |
Isolation | Insulated between DI input and various outputs (not insulated from system and various inputs) |
Program (optional) | |
Registrable pattern | 1 |
Number of steps | 9 maximum |
Program setting range | |
Level | Same as measuring range |
Time | 1~9999 minutes/step |
Ramp | To be set automatically according to level and time |
Number of executions | 9999 maximum |
PID output limiter | To be set selectively from 3 types of PID & output limiter |
External control input | DI/non-voltage 1 point (RUN/RST, HLD, ADV) |
Action status output | RUN, END and STEP to be selectively output to event output |
CH2 and CH3 in SV follow setting | Program to be executed by making CH2 or CH3 deviation-follow to pattern set in CH1 in SV follow setting. Not in SV follow setting, program is executed in FIX mode. |
Additional functions | Temporary suspension (HLD), carryforward (ADV), PV start Analog output (optional, selectable between this function and communication) |
Number of output | 1 |
Output types | Selectable from CH1_PV, CH2_PV, CH3_PV, CH1_SV, CH2_SV, CH3_SV, CH1_OUT, CH2_OUT and CH3_OUT |
Output rating | 0~10mV DC/Output impedance 10? 0~10V DC/Load current 1mA maximum 4~20mA DC/Load resistance 300? maximum |
Output accuracy | ±0.3%FS (to displayed value) |
Output resolution | Approx. 1/8000 |
Output updating cycle | 0.5 seconds |
Output scaling | Within measuring range (inverted scaling possible) |
Isolation | Insulated between analog output and various inputs and system (not insulated between analog output and control outputs I, P and V) |
Communication (optional, selectable between this function and analog output) | |
Communication type | RS-232C, RS-485 |
Communication system | Half duplex start-stop synchronous system |
Communication speed | 1200, 2400, 4800, 9600, 19200bps |
Data format | 7 bits, 8 bits, no parity, even parity selectable |
Communication address | 1~99 |
Communication code | ASCII code |
Communication protocol | Shimaden standard protocol |
Communication format | Control code selectable, BCC check arithmetic system selectable |
Isolation | Insulated between communication signal and system/input/output |
Others | Meets the EMC standards with an additional clamp filter (E04SR301334, SEIWA Information Systems Co.,LTD) |
Others | |
Data storage | By non-volatile memory (EEPROM) |
Ambient temperate/humidity ranges | -10~+50°C/below 90% RH (on condition that there is no dew condensation) |
Temperature for storage | Between-20 and +65 °C |
Power voltage | 100V~260V AC ±10% (50/60 Hz) |
Power consumption | 12VA maximum |
Input noise removal ratio | Normal mode 45 dB minimum (50/60 Hz) Common mode 140 dB minimum (50/60 Hz) |
Applicable standard Safety | IEC1010-1 • EN61010-1 EMC EMI (emission): EN50081-2: 1993 EMS (immunity): EN50082-2: 1995 |
Insulation resistance | Between input/output terminals and power terminal: 500V DC 20MΩ minimum Between input/output terminals and protective conductor terminal: 500V DC 20MΩ minimum |
Dielectric strength | 1 minute at 2300V AC between input/output terminals and power terminal (inductive current 5mA)
1 minute at 2300V AC between power terminal and ground terminal (inductive current 5mA) |
Protective structure | Only front panel has simple dustproof and drip-proof structure |
Material | PPO resin molding (equivalent to UL94V-1) |
External dimensions | 96 x 96 x 110 mm (Panel depth: 100 mm) |
Mounting | Push-in panel (one-touch mount) |
Panel cutout size | H92 x W92 mm |
Weight | Approx. 420 g |
ITEMS | CODE | SPECIFICATIONS | ||||||||
SERIES | MR13- | MPU-Based 3 Channel Auto-Tuning PID Controller DIN 96 × 96mm | ||||||||
INPUT | 1 | Thermocouple B, R, S, K, E, J, T, N, PLII,
WRe5-26, U, L |
Multi-input Multi-range |
|||||||
2 | R.T.D. Pt100 / JPt100 | Multi-range | ||||||||
3 | Voltage (mV) -10-10, 0-10, 0-20, 0-50, 10-50, 0-100mV DC | Multi-input Programmable Range | ||||||||
4 | Current (mA) 0-20, 4-20mA DC | |||||||||
6 | Voltage (V) -1-1, 0-1, 0-2, 0-5, 1-5, 0-10V DC | |||||||||
CONTROL OUTPUT | -Y | Contact: Proportional Cycle 0.5-120.0 sec. Contact capacity: 240V AC 2.5A / resistive load | ||||||||
I1- | Current: 4-20, 0-10mA DC Load resistance: 600Ω max | |||||||||
P1- | SSR drive voltage: Proportional Cycle 0.5-120.0 sec. Output rating: 15V±3V DC / 20mA max | |||||||||
V1- | Voltage: 0-10V DC Load current: 2mA max. | |||||||||
PROGRAM FUNCTION (OPTION) | N | None | ||||||||
P | 1 Pattern, 9 step | |||||||||
EVENT OUTPUT (OPTION) | 0 | None | ||||||||
1 | Contact (1a common): 240V AC 1A / resistive load EV1, EV2, EV3 / 3 Point | |||||||||
REMOTE OR DI INPUT (OPTION) | 00 | None | ||||||||
04 | 4-20mA DC Receiving resistance: 250Ω | |||||||||
05 | 1-5V DC Input resistance: 500kΩ min. | |||||||||
06 | 0-10V DC Input resistance: 500kΩ min. | |||||||||
51 | DI Non-Voltage Contact, Open Collector Input | |||||||||
ANALOG OUTPUT OR
COMMUNICATION FUNCTION (OPTION)
|
00 | None | ||||||||
03 | Voltage 0-10mV DC, Output resistance: 10Ω | |||||||||
04 | Current 4-20mA DC, Load resistance: 300Ω max | |||||||||
06 | Voltage 0-10V DC, Load current: 1mA max | |||||||||
15 | RS-485 | |||||||||
17 | RS-232C | |||||||||
REMARKS
|
0 | Without | ||||||||
9 | With (Please consult before ordering.) |
MR13 Controllers are Shimaden Lite Software Compatible – Software Available “Free”
Product Range
Code | Specifications | Price | Quantity | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
MR13-2Y1-N0 | RTD Input with Contact Output | $960.00 | |||||||||
MR13-2Y1-N1 | RTD Input, Contact Output + Events | $1,080.00 | |||||||||
Intech Instruments Ltd are the New Zealand distributor for Shimaden products. Please contact the Shimaden distributor in your country if you require sales or service support for Shimaden products.