Tech Support: |
To add a 2100-A16-NET to the MicroScan Interface:
(first check that the 2100-A16-NET is configured for the MicroScan Interface)
1. Start MicroScan V5 and click the "Setup Tools" link in the navigation pane and then select the "MicroScan Interface" link:

2. The Port Setup dialog appears:
Set Port to None if no stations are used on local serial port.
Enable the "Ethernet Mode" at the bottom of the dialog.
Click OK.

3. Back on the MicroScan V5 Setup Tools page click on the "Add New Station" link.

4. The Add New Station Wizard dialog appears - click "Next".

5. Select "add a 2100-XX station" and click "Next".

6. Enter in the station serial number and click "Next". If not required select
Station Alarm Relays = Do Not Add.

7. Specify the unit station number as required and click "Next".

8. Enter in the IP Address and the Ethernet Port as configured in the XPort® Installer software, then click "Next".

9. Check the settings and click "Next".

10. The final dialog will appear - click "Finish".
